TML-13kW
Top-mounted liquid-cooled unit
Product Features
- Modular design, compact structure, and space-saving.
- Intelligent control dynamically matches thermal loads with high precision; the unit’s operating status and parameter changes are monitored in real time for enhanced safety and peace of mind.
- Internationally renowned components + Advanced production processes + Improve testing methods + Multiple layers of protection for safety and reliability.
- All-Direct-Current Inverter Technology + The electronic expansion valve features dynamic flow regulation for high efficiency and energy savings.
- Adopt EC/DC Variable-frequency fans for energy saving and noise reduction.
- Uses environmentally friendly and highly efficient refrigerants, ensuring green and eco‑friendly operation.
- Standard automatic liquid replenishment function reduces on-site maintenance.
- Wide cooling capacity range for more flexible selection.
- Supports customization to meet user needs to the greatest extent possible.
Product Parameters
Product Model | YHYL13RDFBPEIIIAS | YHYL13RDTBPDIIIAS |
Rated Cooling Capacity ( kW) | 15 | 15.5 |
Rated Cooling Power Consumption ( kW) | 6.35 | 6.2 |
Rated Cooling Performance Coefficient ( kW/kW) | 2.36 | 2.5 |
Nominal Cooling Capacity ( kW) | 13 | 13.1 |
Nominal refrigeration power consumption ( kW) | 7 | 6.55 |
Nominal Coefficient of Performance (COP) for Refrigeration kW/kW) | 1.86 | 2 |
Electric heating amount ( kW) | 3 | 3 |
Maximum Input Power ( kW) | 8.35 | 7.1 |
Maximum Input Current (A) | 13.2 | 13 |
Air Inlet and Outlet Configuration | Front intake + side exhaust | Forward air + Top exhaust |
Power Supply Type | 380V ±15% ~ 3N 50Hz/60Hz | |
Temperature control accuracy ( °C ) | ±1℃ | |
Display screen (optional) | 4-inch HMI LCD display (optional) | |
Refrigerant Type | R134a | |
Compressor Type | DC Inverter | |
Condenser fan type | EC Centrifugal Fan | DC axial flow fan |
Coolant Type | 50% Ethylene Glycol Aqueous Solution | |
Coolant flow rate ( L/min) | 105 L/min at 100 kPa | |
Inlet/Outlet Port Size | NW32 | |
Fluid Fill/Exhaust Port Size | SM40 Quick Connector | |
Water tank fill port size | SM40 Quick Connector | |
Fluid Reservoir Volume (L) | / | 8 |
Liquid temperature setting range ( °C ) | 5–40°C | |
Operating temperature range ( °C ) | -30 to +60°C | |
Storage environment temperature ( °C ) | -40 to +80°C | |
Working Altitude (m) | ≤4000m; when the altitude exceeds 1000m, performance decreases by 5% for every additional 1000m. | |
Installation Method | Top-mounted horizontal installation | |
External dimensions (width × depth × height) (m) | 1100*1190*430 | 800*1095*460 |
Weight ( kg) | 155 | 132 |
Power supply interface | WP20K5Z-WP20J5TK | |
Communication interface | WP20J12TK-WP20K12Z | |
Communication Methods | RS485 (CAN communication optional) | |
Corrosion Protection Level | C3 (C5 optional) | |
Protection Level | IP54 | |
Shell Material | High‑quality galvanized steel sheet | |
Appearance color | RAL 7035 (customizable) | |
Design Life (years) | 10 years | |
Installation Environment | Outdoors | |
| Note: Designated cooling test conditions: ambient dry-bulb temperature 35°C / wet-bulb temperature —, chilled water outlet temperature 18°C; | ||
| Nominal refrigeration test conditions: ambient dry-bulb temperature 45°C / wet-bulb temperature —, chilled water outlet temperature 18°C; | ||
| Nominal heating test conditions: ambient dry‑bulb temperature —/wet‑bulb temperature —, outlet water temperature 20°C. | ||