TML-6kW
Top-mounted liquid-cooled unit
Product Features
- Modular design, compact structure, and space-saving.
- Intelligent control dynamically matches thermal loads with high precision; the unit’s operating status and parameter changes are monitored in real time for enhanced safety and peace of mind.
- Internationally renowned components + Advanced production processes + Improve testing methods + Multiple layers of protection for safety and reliability.
- All-Direct-Current Inverter Technology + The electronic expansion valve features dynamic flow regulation for high efficiency and energy savings.
- Adopt EC/DC Variable-frequency fans for energy saving and noise reduction.
- Uses environmentally friendly and highly efficient refrigerants, ensuring green and eco‑friendly operation.
- Standard automatic liquid replenishment function reduces on-site maintenance.
- Wide cooling capacity range for more flexible selection.
- Supports customization to meet user needs to the greatest extent possible.
Product Parameters
| Product Model | YHYL06RDFBPEIIBS | YHYL06RDFBPEIIAS | YHYL06RD R BPEIIAS | YHYL06RDTBPDIIAS |
Rated Cooling Capacity (kW) | 6.5 | 6.4 | 7.2 | 7.2 |
Rated Cooling Power Consumption (kW) | 2.75 | 2.6 | 2.75 | 2.88 |
Rated Cooling Performance Coefficient (kW/kW) | 2.36 | 2.46 | 2.62 | 2.5 |
Nominal Cooling Capacity (kW) | 6.0 | 6.0 | 6.8 | 6.8 |
Nominal Cooling Power Consumption (kW) | 3.35 | 3.25 | 3.35 | 3.4 |
Nominal Coefficient of Performance (kW/kW) | 1.79 | 1.85 | 2.03 | 2 |
Electric heating capacity (kW) | 2 | 2 | 2 | 2 |
Maximum Input Power (kW) | 3.6 | 3.65 | 3.45 | 3.65 |
Maximum Input Current (A) | 17.5 | 17.5 | 15.5 | 17.5 |
Air Inlet and Outlet Configuration | Side (Rear) Air Inlet + Front Air Outlet | Side (Rear) Air Inlet + Front Air Outlet | Front intake + rear exhaust | Forward air + Top exhaust |
Power Supply Type | 220V ±15% ~ 1N 50Hz/60Hz | |||
Temperature control accuracy (°C) | ±1℃ | |||
Display screen (optional) | 4-inch HMI LCD display (optional) | |||
Refrigerant Type | R410A | R134a | ||
Compressor Type | DC Inverter | |||
Condenser Fan Type | EC Centrifugal Fan | DC axial flow fan | ||
Coolant Type | 50% Ethylene Glycol Aqueous Solution | |||
Coolant flow rate (L/min) | 50 L/min at 100 kPa | |||
Inlet/Outlet Port Size | NW26 | |||
Fluid Fill/Exhaust Port Size | SM40 Quick Connector | |||
Water tank fill port size | SM40 Quick Connector | |||
Fluid Reservoir Volume (L) | 2.5 | 3.5 | ||
Liquid Temperature Setting Range (°C) | 5–40°C | |||
Operating Temperature Range (°C) | -30 to +60°C | |||
Storage environment temperature (°C) | -40 to +80°C | |||
Working Altitude (m) | ≤4000m; when the altitude exceeds 1000m, performance decreases by 5% for every additional 1000m. | |||
Installation Method | Top-mounted horizontal installation | |||
External dimensions (width × depth × height) (mm) | 780*1030*280 | 780*1030*280 | 785*1245*330 | 785*1075*355 |
| Weight (kg) | 85 | 88 | 112 | 96 |
Power supply interface | WY20J3TE-WY20K3Z | |||
Communication interface | WY20J9TE-WY20K9Z | |||
Communication Methods | RS485 (CAN communication optional) | |||
Corrosion Protection Level | C3 (C5 optional) | |||
Protection Level | IP54 | |||
Shell Material | High‑quality galvanized steel sheet | |||
Appearance color | RAL 7035 (customizable) | |||
Design Life (years) | 10 years | |||
Installation Environment | Outdoors | |||
Note: Designated cooling test conditions: ambient dry-bulb temperature 35°C / wet-bulb temperature —, chilled water outlet temperature 18°C; | ||||
| Nominal refrigeration test conditions: ambient dry-bulb temperature 45°C / wet-bulb temperature —, chilled water outlet temperature 18°C; | ||||
| Nominal heating test conditions: ambient dry‑bulb temperature —/wet‑bulb temperature —, outlet water temperature 20°C. | ||||