Product Categories
Detailed information
HP2-104/156
Integrated On-Grid and Off-Grid Photovoltaic Storage System
Product Features
Seamless Off-Grid Switching
- Integrate static transfer switch functionality
- Millisecond-level (<20ms) switching
- The photovoltaic DC bus directly supplies power to the energy storage system.
- Natively supports off-grid operation.
- Suitable for scenarios with unstable power grids and high requirements for power supply reliability.
Modular Redundancy
- Internal Coordinated Control of Hybrid Inverters
- Supports capacity adjustments based on changing project requirements.
- Highly integrated, featuring mature BMS, EMS, and fire protection systems.
- 20-year design life with exceptional environmental adaptability, capable of handling a wide range of operating conditions.
- Standardized design, integration, transportation, expansion & installation, and operations & maintenance.
Product Parameters
It employs square lithium iron phosphate 314 Ah cells with a long cycle life and utilizes a flexible DC coupling solution featuring a hybrid inverter with redundancy capabilities. The photovoltaic array feeds DC power directly into the DC bus via an MPPT controller, where it is coupled with the energy storage battery system on the DC side, before being converted back to AC power by a centralized hybrid inverter for load use.
Product Model | HP2-104-HBPV | HP2-104-HBPV | HP2-156-HBPV |
PV Photovoltaic Parameters | |||
Maximum PV Current (A) | 64/64 | 42/32/42/32 | 42/32/42/32 |
MPPT Voltage Range (V) | 200–800 | 160–850 | 160–850 |
Maximum PV Voltage (V) | 850 | 1000 | 1000 |
Number of PV Connection Paths | 2 | 4 | 4 |
AC Output Parameters | |||
Rated Output Power (kW) | 30 | 50 | 50 |
Output Voltage (V) | 230/400 | 380/400 V | 380/400 V |
Power grid frequency range (Hz) | 50/60 | 50/60 | 50/60 |
Output Harmonics (V, Off-Grid) | <3% | <3% | <3% |
Maximum efficiency | 97.8% | 98.1% | 98.1% |
Battery-side parameters | |||
Cell Capacity (Ah) | 314 (0.5P) | 314 (0.5P) | 314 (0.5P) |
Rated Voltage (VDC) | 332.8 | 332.8 | 499.2 |
DC Voltage (VDC) | 291.2–374.4 | 291.2–374.4 | 436.8–561.6 |
Battery Pack Configuration | 1P104S | 1P104S | 1P156S |
Battery life (cycle) | 6000 @ 100% DOD, 70% SOH, 25°C | ||
Single‑box capacity (kWh) | 104 | 104 | 156 |
Environmental parameters | |||
Charge and discharge efficiency (%) | ≥95% | ||
Operating Temperature Range (°C) | -30°C to 55°C | ||
Storage Temperature Range (°C) | -40℃~60℃ | ||
Operating Humidity Range (%) | <95%, no condensation | ||
Maximum Operating Altitude | ≤4000 m (derate above 3000 m) | ||
Cooling Method | Liquid cooling | ||
Fire Fighting System | Aerosol | ||
Other parameters | |||
Weight (T) | ≤2 tons | ||
Dimensions (Width × Depth × Height, mm) | 1050mm*1350mm*2050mm | ||
Protection Level | IP55 | ||
Online Quotation Request